An ordinance of the City of ,Harysville supplementing
the combined ~Jater and dewar 'System Code by amending
3ection 2.03 of Article II of,the Hater 5ystem Code.'
Tft::CITY COUJ:~CIL OF TH1 CITY OF HARYSVILV];DO ORDA.H~AS FOLLOHs'l
'rticle'11 Water Code
3ection 2.03 Fire Hydrants,Tees,Gate Valves and Blow-off'
Section 1.Definitions,
a.Approving authority"-the approving author-Ley
for the several"requirements of this ordinance shall be the Fire'
Chief,':later,Department SuperintEmdent'and City Engineer'.'
b.Pub l.Lc Hydrant ,;"a 'public hydrant 1.S 'a fire'
.'
hydrant so situated and maintained as to'provide'water for fire
fighting purpo's~s without res trictiori 'as'to 'use.The Locatn.on Ls
such that it is accessible for immediate use of the fi~e de~artment.
c.Private Hydrant -a private hydrant is a f,ire
hydrant so situated and maintained as to prqvide water for fire
fighting purposes ,with restrictions for its use limited to certain
defined pr-opezcy or prqperties..the location may be such that it
is not readily accessible for immediate use of the responding fire
department or departments.
d..Fire Department -the.term ufire'depar-tment;"shall
mean the Fire Department of the City of Marysvill~and/or any
recognized fire department,'normal}y'responding in the area,'to
-"1
/'
..'
,.'.'..
include private fire brigades o~ga~ized,trained and'equipped to'
prdtect'specified property.
e.Co~mercial and industri~l properties shall include,
but not necessarily be limited to,retail and.wholesale stores,
'warehou'ses,service stations,manuf actiur-Lng facilities,gaz-age s ,
theaters,hotels,motels,restaurants~bars and taverns"banks,
ahowr-ooms ,barber and ','beauty shops.
f.Institutional pr-opez-t Les 'include,but are not
necessarily limited to,'places.of \1Torship,private schools,parochial
s chooLs , Lns t Ltiut i.ons of higher learning,'public and private hosp LtiaLs ,
nursing homes;lodges.~nd fraternal,orders,unless the structure.".
contains a function of a conunercial or industrial nature.
g.Public properties shall include civic'buildings,
public schools,'playgrounds,public parks and appurtenances.
',h.Residential properties,are those intended for'
human habitation.i:!henever the words "s LngLe f,amily dwelling"are
used herein they shall also'i,nclude ,th~structure known as a,'
"duplex"-,two-family dwelling.'A residence constructed and equipped
,for occupancy by more''than two 'familie,s shall be defined,as a
multi-family dwelling or high density dwelling"the terms being
identical in meaning.
1.Fire fio~7~'fire ,flow is,the amount of water
required to extin~uish a fire.For the purpose of this ordinance
the requirement -shall be applied by flow tests made at or in the
vicinfty of·the ,installation.
dection 2.The installation of fire ,hydrants in accordance
\'-.
\1 ..
with this ordinance shall be required of the owner and/or developer
~f any,future bus Lnes s ,commer-ct.a I ,'instit:ut'ional .or Lndus trnLa L
facility,dwelling or dwelling development,.
Section 3.,\11 fire hydr ant s installed as'required by this
ordinance shall be served by the'Ci~y ot ~Iarysville JJ"ater Depar tmen t
unless conditions warrant a 'waiver of this provision.
3ect1.on 4.The,installation of.private hydrants as gefined..".,.. .
herein shall be limited to:those cases when the'number:of,~Ublic
hydrants ins tra Ll ed under the'distance provisions of,this ordinance"
Shall be insufficient in number.Private hydr.ants s ha l.l.i mee t;City
req\lirements for public hydrants and shall be located,as designated
by the approving authority.'The City of'Narysv.~lle shall have ,the
right to go upon .rhe premises and to use the private hydrant'for
public purposes"including testing,flushing and emeFgency uses.,
,ection 5.Allcotnmer,ciai,industrial,Lns t Ltiu't Lona L and
public properties shall provide ~dequate fire protection as prescribed
hereaf~er.As recommended by the approving authority,any or all
"
of the above propertias Shall have a looped fire protection lirie
ar-ound the property.'The Loop may be a part of,the eXisting supply'
sys rem,'The size of the'loop shall be no'less than six inches and'
,shall be sized to the 'fire flowsestimatedaccox::ding to the
fJashington Surveying and Rating Bureau or as modified by the City
:,~ngineer.~"ire hydrants shall be,installec;i on'the ,loop at noumoxe
than 300 feet apart as'measured a~ong the watermain.
Se~tion 6.Fire hydrants ~hall be installed on all extensions
"of the City tl~ter Sys~em at the time such extensions are cons trruc ted,,
....s,r
------------------
~
:1ydrants'shall be installed a t each,intersection of a street or
public road and at such intermediat~,points as will 'result 'in
spacing between hYdrants in residential areas of not to exceed 600
feet)measured along road centerlines,EXCEPT as 'follows:'
a.If adja~ent road o~street interse~tions are
spaced at 1/8 mile (660')intervals the hydrant spacing may also
be 1/8 mile.
b.The hydrant may be omitted at an intersection if:
(1)The sum of the two greatest distances from
the center of that intersectiont6 the ~enter of adjacent inter~ections
(where hydrants are existing or proposed or where no ~ater mains
exist)in all directions is less than 600 feet;or
,(2)The sum of the.distances to the center of
the two adjacent intersections along the extension is less than
600 feet and the distances on the cross street to the·first inter-
sections in both direc~ions ~re'both mbre than'660 feet.
c.In general,all hydrants are to be located 6.0
feet from the right-of-way line in a 50 or 60 footh right-of-way
and 1.0 f oot;from the 'right-'of-way line in a 40 foot right-of-way.'
Section 7.Fire hydrants shall also be installed at the ends
of the deadend lines which are more than 300 feet in length.Said'
hydrants may later be moved to cQnform t~standard spacing requirements
vYhen the main 'is again extended"under supervision of the Superintendent.,
3ection'8.The ,buildings having r~quired fire flow of less,
than 2500 gpm (other than building~of fire resistive construction)
..
shall have'fire hydz-arrt s on one,side of the building only,yet there
4, -
..~
shall never,be less than two (2)fire hydrants available for an¥
building 'larger than 5,000 square:feet of ground area •.Location
of hydrants protecting buildings requiring fire'flows larger than
2500 gpm shall be determined .by'approving authority".
Section 9.All hydrants ~hall standpl~b,be ~et,to the
estab1ishedgrade with the10west out1et'ofthe hydrant no less
than eighteen'(18)Lnches above the grade and no leas than'thirty-
six (36)inches of clear area about th~hydrant for clearance of,
the hydrant ~rrench on both outlets and on the control valve.The
pumper port shall face the street •tJhere the street'cannot be
clearly defined or recognized,the port shall face the most like~y
route ofapproa.ch ami location of the fire truck while pumping,
this to be determined by the approving authority.
Section 10.If the 'use of the property changes~the existing
hydrants shall be updated to c.onform to the:requirements of this
section of the code.
:Sec~ion 11.,.Three port hydz-antrs;shall be installed on ali"
"Jater extensions ~rid existing mains serving commercial,Lndus tz-Le I',
<,'"•••,•','.'
institutional and public'properties •.All o~her a~eas sh~ll have.'
two port hydrants installed.
Section 12.Noone shall plant any vegetation,'erect any.
structure or perform any action which re~~lts in ob~tructing the:'
vi~w of a fire hydrant for a distance,6f'fifty (50)feet.The
ov:rner andlor occupant of any area itl'which a,'hydrant is locat~d
shal.l be responsi.'b~e for removing weed ,arid tree growth from around
the hydrant.for a dis t ance of not 1es~than ten (10),feet.The'
5
,,.-'.
",'"
purpose 'of this section is to maintain a,~lear visual area around
the hydrant.
Section 13.,Nobui·lding..permits shall be'issued for erection
of any.bui~ding or structure until.reasonable pl;"oof of intent to
comply with this ordinance is indicated'and ·the approving authority
is s~tisfied'thai:hydrants are to be installed to comply ll1ith this
ordin.a.nce.
'B,•.Blow-off valves shall be installed at the end of all
dead-end lines less than 300 feet ,in length unle~s a fire hydrant
is provided at ,that point.A b~ow~off assembly shall conform to
~arysville ~tandard Detail or be~pproved by the5uperintendent.
C.Gate valves or '(vater control'valves.A gate valve shall
..
be located at the end of all dead-end lines in which a future
extension is anticipated by.the City Enginee~.Gate valves may.
be required on the ends of dead tees or crosses at the discretion
of the City ~ngineer.
.'
D.Tees and crosses.Tees and crosses shall be provided at
all street crossings v:rhere future extensions might develop or,wher-e
the City anticipates a line may be installed for the purpose of
improVing circulation in the system.
Section 14.Compliance with all ~onditionsof this and
existing city ordinances shall be'req1.,1~red for connecting to city
mains.
Section 15.Violations of this:ordinance shall ,be punishable
by .a .fine of up to ~300.00,or imprisortme.~t·for up to ninety (90)
days or'by such fine and imprisonment~·
-
....'<;."(..v
'l"-:'.
"'".,'""~.,'...-"
~ection 16 •.This ordinance shall take effect from apd after
its passage,approval and five days f9l1~wi~g'it.s publication as
required by l~w.