HomeMy WebLinkAboutO-2875 - Adds new Ch. 9.04; repeals Ords. 2378, 2532 and 2739, fire code (9.04)CITY OF MARYSVILLE
Marysville, Washington
ORDINANCE NO. Ji5J« ,
AN ORDINANCE OF THE CITY OF MARYSVILLE REPEALING AND
REPLACING PORTIONS OF ORDINANCES NO. 2739, NO. 2532, AND
NO. 2378 CODIFIED IN MARYSVILLE MUNICIPAL CODE CHAPTER
9.04; AND ADOPTING A REVISED AND UPDATED MARYSVILLE
MlJNICIPAL CODE CHAPTER 9.04 ENTITLED "FIRE CODE"; AND
PROVIDING FOR SEVERABILITY.
WHEREAS, the City desires to revise and update the Marysville Municipal Code (MMC)
Chapter 9.04 entitled "Fire Code" to the 2009 International Fire Code and to have MMC
section numbers consistent with the International Fire Code, the City repeals Chapter
9.04 and adopts a new Chapter 9.04 entitled "Fire Code."
NOW, THEREFORE, THE CITY COUNCIL OF THE CITY OF MARYSVILLE,
WASHINGTON DO ORDAIN AS FOLLOWS:
Section 1. Repeal. Portions of Ordinances No. 2739, No. 2532, and No. 2378 codified in
Marysville Municipal Code Chapter 9.04 entitled "Fire Code" are hereby repealed.
Section 2. Adopt. A New Marysville Municipal Code Chapter 9.04 entitled "Fire Code"
is hereby adopted to be codified to read as follows:
Chapter 9.04
FIRE CODE
Sections:
9.04.0010 Adoption by reference.
9.04.0020 Establishment and duties of bureau of fire prevention.
9.04.0030 Definitions.
9.04.0040 Flammable or combustible liquid storage limits
9.04.0070 Additional amendments to International Fire Code.
9.04.0101 International Fire Code Appendices Adopted
9.04.0105 International Fire Code Section 105 Permits is amended.
New Section 105.7.15 added -Solar photovoltaic power systems
9.04.0109.3 Violation Penalties -Amended International Fire Code Section 109.3
9.04.0109.4 Section 109.4 -Excessive False Alarms, Penalty Imposed
9.04.0503 Additional sections of International Fire Code Section 503 adopted -Fire
Apparatus Access Roads.
9.04.0503.1.4 Section 503.1.4 added -Aerial Fire Apparatus Access Roads.
9.04.0503.1.5 Section 503.1.5 added -One-or Two-Family Dwelling Residential
Developments.
9.04.0503.2 International Fire Code Section 503.2 amended -Access -Specifications:
ORDINANCE Page 1 of 13
glrnv/MV-II-021/IFC/Ord Ch 9 04 Fire Code 07-22-11 F
9.04.0503.2.3 International Fire Code Section 503.2.3 amended -Access -Surfacing.
9.04.0503.2.4 International Fire Code Section 503.2.4 amended -Access -Turning radius.
9.04.0503.2.5 International Fire Code Section 503.2.5 amended -Access -Turnarounds.
9.04.0503.2.7 International Fire Code Section 503.2.7 amended -Access -Gradients.
9.04.0503.5 International Fire Code Section 503.5 amended -Required gates or
barricades.
9.04.0503.6 International Fire Code Section 503.6 amended -Gates accessing residential
developments.
9.04.0503.7 International Fire Code new Section 503.7 added -Split entries.
9.04.0505 International Fire Code Section 505.1 Address identification is amended.
9.04.0507.3 International Fire Code Section 507.3 Fire flow is amended.
9.04.077.1 International Fire Code Section 511 added.
9.04.0507.5 International Fire Code Section 507.5.1 fire hydrant location is not adopted.
9.04.0601 International Fire Code Section 601.2 Permits is amended. Solar photovoltaic
power systems permit is added.
9.04.0602 International Fire Code Section 602. I Definitions is amended added
definition -Power tap.
9.04.0605 New International Fire Code Section 605 Electrical equipment is amended.
9.04.0902 International Fire Code Section 902.1 Definitions is amended.
9.04.0903 International Fire Code Section 903.2 amended -Sprinkler systems -Where
required
9.04.0903.2.1 International Fire Code Section 903.2.1 amended -Sprinkler systems
Group A occupancies.
9.04.0903.2.3 International Fire Code Section 903.2.3 amended -Sprinkler systems
Group E occupancies.
9.04.0903.2.4 International Fire Code Section 903.2.4 amended -Sprinkler systems
Group F-1 occupancies.
9.04.0903.2.7 International Fire Code Section 903.2.7 amended -Sprinkler systems
Group M and B occupancies.
9.04.0903.2.8 International Fire Code Section 903.2.8 amended -Sprinkler systems
Group R occupancies.
9.04.0903.2.9 International Fire Code Section 903.2.9 and 903.2.10 amended -Sprinkler
systems -Group S occupancies.
9.04.0010 Adoption by reference.
Certain documents, copies of which are on file in the office of the clerk of the city of Marysville,
entitled "International Fire Code, 2009 -Edition," (IFC) published by the International Code
Council, with amendments as adopted by the Washington State Building Code Council are
adopted as the fire code of the city of Marysville (hereinafter sometimes referred to as the "fire
code") for the purpose of prescribing regulations for the safeguarding of life and property from
the hazards of fire and explosion. Except as otherwise specifically amended herein, or by later
ordinance, each and all of the regulations, provisions, penalties, conditions and terms of said
code and standards are incorporated and made part of this chapter as if fully set forth herein.
(Formerly 9.04.010, Ord. 2739 § 1,2008; Ord. 2532 § 1,2004; Ord. 2378 § 1,2001).
ORDINANCE Page 2 of 13
glmvIMV-II-021/IFC/Ord Cil 9 04 Fire Code 07-22-11 F
9.04.0020 Establishment and duties of bureau of fire prevention.
(I) The International Fire Code shall be enforced by the bureau of fire prevention in the fire
department of Marysville which is established and which shall be operated under the supervision
of the chief of the fire department.
(2) The fire marshal in charge of the bureau of fire prevention shall be the chief of the fire
department of Marysville, or any qualified person designated by the chief.
(3) The chief of the fire department may detail such members of the fire department as inspectors
as shall from time to time be necessary.
(Formerly 9.04.020; Ord. 2739 § 1,2008; Ord. 2532 § 2, 2004; Ord. 850 § 2, 1975).
9.04.0030 Definitions.
(1) Wherever the word "jurisdiction" is used in the International Fire Code, it means the city of
Marysville.
(2) "Commercial occupancy" means groups A, B, E, H, F, I (except adult family homes as
defined in Chapter 70.128 RCW), M, R-l, R-2, R-4 and S occupancies as defined in Section 202
-Occupancy Classifications of the International Fire Code 2009-Edition.
(Formerly 9.04.030; Ord. 2739 § 1,2008; Ord. 2532 § 3,2004; Ord. 2378 § 2, 2001; Ord. 850 §
3, 1975).
9.04.0040 Flammable or combustible liquid storage limits.
The storage of Class I, II and III-A liquids in aboveground tanks exceeding 26,000 gallons
individual or 78,000 gallons aggregate capacity is prohibited within the corporate limits of the
city of Marysville. Storage shall be limited to horizontal-tanks only. This language shall replace
the language of International Fire Code Sections 3404.2.9.§.~.1 and 3406.2.4.4.
(Formerly 9.04.040; Ord. 2739 § 1,2008; Ord. 2532 § 4, 2004; Ord. 2378 § 3,2001; Ord. 1373 §
2, 1984; Ord. 1082 § 2, 1979; Ord. 850 § 4, 1975).
9.04.0070 Additional amendments to the International Fire Code.
The additional amendments to the fire code in MMC 9.04.0101 through 9.04.0903.2.9 are
enacted.
(Formerly 9.04.070; Ord. 2739 § 1,2008; Ord. 2532 § 7,2004; Ord. 2378 § 6, 2001).
9.04.0101 International Fire Appendices Adopted.
These appendices of the International Fire Code are hereby adopted: B, F, H, I, and J.
(Formerly 9.04.087 Ord. 2739 § 1,2008; Ord. 2532 § 7, 2004; Ord. 2378 § 6, 2001).
9.04.0105 International Fire Code Section 105 Permits is amended. New Section 105.7.15
added -Solar photovoltaic power systems.
105.7.15 Solar photovoltaic power systems. A construction pennit is required to install or modify
solar photovoltaic power systems.
9.04.0109.3 Violation Penalties -Amended International Fire Code Section 109.3
(1) Any person who violates any of the provisions of this code as adopted or fails to comply
therewith, or who violates or fails to comply with any order made under this code, or who builds
in violation of any detailed statement of specifications or plans submitted and approved
ORDINANCE Page 3 of 13
g/mv/MV-II-021/IFC/Ord Ch 9 04 Fire Code 07-22-11 F
thereunder, or any certificate or permit issued thereunder, and ITom which no appeal has been
taken, or who fails to comply with such an order as affirmed or modified by the chief or by a
court of competent jurisdiction within the time fixed in this chapter is severally, for each and
every such violation and noncompliance respectively, guilty of a misdemeanor, punishable by a
fine of not more than $1,000.00 or by imprisonment for not more than 90 days, or by both such
fine and imprisonment. The imposition of one penalty for any violation shall not excuse the
violation or permit it to continue; and all such persons shall be required to correct or remedy
such violations or defects within a reason-able time; and when not otherwise specified, each 10
days that prohibited conditions are maintained constitutes a separate offense.
(2) The application of the penalties herein described shall not be held to prevent the enforced
removal of prohibited conditions.
(Formerly 9.04.100; Ord. 2739 § 1,2008; Ord. 2532 § 10,2004; Ord. 850 § 10, 1975).
9.04.0109.4 Section 109.4 -Excessive False Alarms, Penalty Imposed.
No more than three false alarms from any location shall be permitted within any calendar year.
The owner or operator of any location from which more than three false alarms are sent within
any calendar year shall be subject to the imposition of a criminal penalty pursuant to MMC
9.04.0109.3.
(Formerly 9.04.095; Ord. 2739 § 1,2008; Ord. 2532 § 9,2003).
9.04.0503 Additional sections of International Fire Code Section 503 adopted -Fire
Apparatus Access Roads.
Section 503.1 shall be adopted as written, Sections 503.1.1, 503.1.2, 503.1.3, 503.2, 503.3, and
503.4, being sections of the International Fire Code (20026 Edition) not adopted by the
Washington State Building Code Council, are hereby adopted and enacted in the city of
Marysville.
(Formerly 9.04.071; Ord. 2739 § 1,2008; Ord. 2532 § 7,2004; Ord. 2378 § 6,2001).
9.04.0503.1.4 Section 503.1.4 added -Aerial Fire Apparatus Access Roads.
503.1.4 Where Required. Buildings or portions of buildings or facilities exceeding 30 feet (9,144
mm) in height above the lowest level of fire department vehicle access shall be provided with
approved fire apparatus access roads capable of accommodating fire department aerial apparatus.
Overhead utility and power lines shall not be located within the aerial fire apparatus access
roadway.
503.1.4.1 Width. Fire apparatus access roads shall have a minimum unobstructed width
of26 feet (7,925 mm) in the immediate vicinity of any building or portion of building
more than 30 feet (9,144 mm) in height.
503.1.4.2 Proximity to building. At least one of the required access routes meeting this
condition shall be located within a minimum of 15 feet (4,572 mm) and a maximum of 30
feet (9,144 mm) from the building, and shall be positioned parallel to one entire side of
the building.
(Formerly 9.04.076.1; Grd. 2739 § 1,2008).
ORDINANCE Page 4 of 13
g/mvIMV-II-021/IFC/Ord Ch 904 Fire Code 07-22-11 F
9.04.0503.1.5 Section 503.1.5 added -One-or Two-Family Dwelling Residential
Developments.
503.1.5 Developments of one-or two-family dwellings where the number of dwelling units
exceeds 30 shall be provided with separate and approved, unobstructed fire apparatus access
roads and shall be placed a distance apart equal to not less than one half of the length of
maximum overall diagonal dimension of the property or area to be served, measured in a straight
line between accesses.
Exceptions:
1. Where there are more than 30 dwelling units on a single public or private fire
apparatus access road and all dwelling units are equipped throughout with an approved
automatic sprinkler system in accordance with Section 903.3.1.1,903.3.1.2 or 903.3.1.3
access from two directions shall not be required.
2. The number of dwelling units on a single fire apparatus access road shall not be
increased unless fire apparatus access roads will connect with future development, as
detennined by the fire code official.
(Formerly 9.04.076.2; Ord. 2739 § 1,2008).
9.04.0503.2 International Fire Code Section 503.2 amended -Access -Specifications:
Section 503.2.1 Dimensions is amended to add:
Where a fire hydrant or fire department connection is located on a fire apparatus access road, the
minimum road width shall be increased to 26', extending 20' on either side of a fire hydrant or
fire department connection.
(Formerly 9.04.072.1; Ord. 2739 § 1,2008).
9.04.0503.2.3 International Fire Code Section 503.2.3 amended -Access -Surfacing.
Section 503.2.3 adopted by MMC 9.04.0503 is further amended to add an additional sentence
reading as follows: "The surface shall be entirely composed of gravel, crushed rock, asphalt or
concrete, and designed to support the imposed load of fire apparatus weighing at least 75,000
pounds."
(Formerly 9.04.073; Ord. 2739 § 1,2008; Ord. 2532 § 7,2004; Ord. 2378 § 6, 2001).
9.04.0503.2.4 International Fire Code Section 503.2.4 amended -Access -Turning radius.
Section 503.2.4 adopted by MMC 9.04.0503 is further amended to add an additional sentence
reading as follows: "A turning radius will be approved only ifit is in accordance with the
Engineering Design and Development Standards for the City of Marysville."
(Formerly 9.04.074; Ord. 2739 § 1,2008; Ord. 2532 § 7,2004; Ord. 2378 § 6,2001.).
9.04.0503.2.5 International Fire Code Section 503.2.5 amended -Access -Turnarounds.
Section 503.2.5 adopted by MMC 9.04.0503js further amended to add an additional three
sentences reading as follows:
Turnarounds shall be a minimum eighty (80) foot diameter cul-de-sac with no obstructions
within the cul-de-sac. Planters may be installed in cul-de-sacs when the outside radius of the cul
de-sac is a minimum of fifty (50) feet and inside radius is minimum of25 (twenty five) feet. An
approved hammerhead turnaround may be used if there are no alternatives, and it is approved by
the Fire Chief.
ORDfNANCE Page 5 of 13
g/nw/MV-ll-021/IFC/Ord Ch 9 04 Fire Code 07-22-11 F
(Formerly 9.04.075; Ord. 2739 § 1,2008; Ord. 2532 § 7,2004; Ord. 2378 § 6, 2001.).
9.04.0503.2.7 International Fire Code Section 503.2.7 amended -Access -Gradients.
Section 503.2.7 adopted by MMC 9.04.0503 is further amended to add an additional sentence
reading as follows: "A gradient will be approved only if it is in accordance with the Engineering
Design and Development Standards for the City of Marysville."
(Formerly 9.04.076; Ord. 2739 § 1,2008; Ord. 2532 § 7,2004; Ord. 2378 § 6, 2001.).
9.04.0503.5 International Fire Code Section 503.5 amended -Required gates or
barricades.
Section 503.5 is amended by adding:
Entrances to roads, trails or other access ways which have been closed with gates and barriers
shall not be obstructed by parked vehicles.
(Formerly 9.04.076.3; Ord. 2739 § 1,2008).
9.04.0503.6 International Fire Code Section 503.6 amended -Gates accessing residential
developments.
Section 503.6 is amended by adding:
Gates installed in a residential community shall be equipped with a strobe activating device.
Minimum gate width opening shall be 20 feet. The gate is required to open automatically with
the approach of emergency vehicles. In the event of a loss of power, the gate shall open
automatically and remain in the open position until power is restored. The gate shall remain in
the open position until such time that the power is restored.
Exemption: 5 or fewer dwelling units.
(Formerly 9.04.076.4; Ord. 2739 § 1,2008).
9.04.0503.7 International Fire Code new Section 503.7 added -Split entries.
Section 503.7 Split Entries.
Split entries to plats, short plats, commercial development and other sites requiring emergency
vehicle access, shall be allowed where each aisle (lane) is at least 14 (fourteen) feet in width.
(Formerly 9.04.076.5; Ord. 2739 § 1,2008).
9.04.0505 International Fire Code Section 505.1 Address identification amended.
Section 505.1 is amended to add the following:
(1) Address numbers for commercial buildings to be a minimum of six inches high with a
principal stroke of at least three-quarters inch.
(2) Where the building is not visible from the street or a single access road or private roadway
serves more than one building, provision shall be made to clearly identify which driveway or
roadway serves the appropriate address.
(3) Address numbers at least four inches high shall be prominently displayed on rear entrance or
access doors when required by the fire code official.
(4) Interior and exterior access doors or individual dwelling, housekeeping, living units, or
commercial tenant spaces also shall be clearly marked. Numbers and/or letters of such units shall
be at least four inches high.
ORDINANCE Page 6 of 13
g/mvIMV-II-021/IFC/Ord Ch 9 04 Fire Code 07-22-11 F
(5) Address Numbering Size Table
Distance from road
or Fire Lane Minimum Size
0-50 feet 4"
51-100 feet 6"
101-150 feet 8"
151-200 feet 10"
201-300 feet 12"
301 feet and up 18"
Four inch numbers are pennitted for single-family and duplex occupancies only. The minimum
size figure for commercial occupancies is six inches. The height to width ratio of the figures
shall be approximately 2H: 1W.
(Formerly 9.04.076.7; Ord. 2739 § 1,2008).
9.04.0507.3 International Fire Code Section 507.3 Fire flow is amended.
(1) Replace "by an approved method" with "per Appendix B of the International Fire Code."
(2) Exceptions. Section 507.3 is amended to add two exceptions reading as follows:
Exceptions:
(2) Subdivisions and short subdivisions in which all lots have a lot area of 43,560 square
feet (one acre) or more in size;
(3) Structures where under the International Building Code the occupancy is classified as
group U occupancies (agricultural buildings, private garages, carports and sheds) that are
restricted to private residential use only. Riding arenas or other agricultural structures
used or accessed by the general public shall not fall within this exception.
(Formerly 9.04.077; Ord. 2739 § 1,2008; Ord. 2532 § 7,2004; Ord. 2378 § 6, 2001.).
9.04.0507.5 International Fire Code Section 507.5.1 fire hydrant location is not adopted.
Fire hydrant locations to be installed per MMC 14.03.050.
(Formerly 9.04.072; Ord. 2739 § 1,2008; Ord. 2532 § 7,2004; Ord. 2378 § 6,2001.).
9.04.0510 International Fire Code Section 510 Emergency Responder Radio Coverage is
amended to include adoption of Appendix J.
9.04.0601 International Fire Code Section 601.2 Permits is amended. Solar photovoltaic
power systems permit is added.
Section 601.2 is amended by adding:
A construction pennit is required to install or modify Solar photovoltaic power systems as set
forth in Section 105.7.
9.04.0602 International Fire Code Section 602.1 Definitions is amended -Power tap.
Add definition to Section 602.1 :
ORDINANCE Page 7 of 13
g/rnv/MV-II-021/IFC/Ord Ch 9 04 Fire Code 07-22-11 F
Power Tap means a listed device for indoor use consisting of an attachment plug on one end of a
flexible cord and two or more receptacles on the opposite end, and has overcurrent protection.
(Formerly 9.04.076.6; Ord. 2739 § 1,2008).
9.04.0605 International Fire Code Section 605 Electrical equipment is amended to add
605.11 :
Section 605.11 added -Solar Photovoltaic Power Systems:
605.11 Solar Photovoltaic Power Systems. Solar photovoltaic power systems shall be
installed in accordance with this code, the International Building Code and NFPA 70.
605.11.1 Marking. Marking is required on all interior and exterior dc conduit,
enclosures, raceways, cable assemblies, junction boxes, combiner boxes, and disconnects.
605.11.1.1 Materials. The materials used for marking shall be reflective, weather
resistant and suitable for the environment. Marking as required in sections 605.11.1.2
through 605.11.1.4 shall have all letters capitalized with a minimum height of 3/8 inch
(9.5 mm) white on red background.
605.11.1.2 Marking content. The marking shall contain the words WARNfNG:
PHOTOVOLTAlC POWER SOURCE.
605.11.1.3 Main service disconnect The marking shall be placed adjacent to the main
service disconnect in a location clearly visible from the location where the disconnect is
operated.
605.11.1.4 Location of Marking. Marking shall be placed on all interior and exterior dc
conduit, raceways, enclosures and cable assemblies every 10 feet (3048 mm) within 1
foot (305 nun) of all turns or bends and within 1 foot (305 mm) above and below all
penetrations of roof/ceiling assemblies and all walls and lor barriers.
605.11.2 Locations of DC conductors. Conduit, wiring systems, and raceways for
photovoltaic circuits shall be located as close as possible to the ridge or hip or valley and
from the hip or valley as directly as possible to an outside wall to reduce trip hazards and
maximize ventilation opportunities. Conduit runs between sub arrays and to DC combiner
boxes shall be installed in a manner that minimizes total amount of conduit on the roof by
taking the shortest path from the array to the DC combiner box. The DC combiner boxes
shall be located such that conduit runs are minimized in the pathways between arrays. DC
wiring shall be installed in metallic conduit or raceways when located within enclosed spaces
in a building. Conduit shall run along the bottom ofload bearing members.
605.11.3 Access and pathways. Roof access, pathways, and spacing requirements shall be
provided in order to ensure access to the roof; provide pathways to specific areas of the roof;
provide for smoke ventilation operations; and to provide emergency egress from the roof.
Exceptions:
ORDfNANCE Page 8 of 13
glmv/MV-l J-02 JIlFC/Ord Ch 9 04 Fire Code 07-22-11 F
I. Requirements relating to ridge, hip, and valleys do not apply to roofs slopes of
two units vertical in twelve units horizontal (2: 12) or less.
2. Residential structures shall be designed so that each array is no greater than ISO
feet (45720 mm) by 150 feet (45720 mm) in either axis.
3. The fire chief may allow panels/modules to be located up to the ridge when an
alternative ventilation method acceptable to the fire chief has been provided or
where the fire chief has detennined vertical ventilation techniques will not be
employed.
605.11.3.1 Roof access points. Roof access points shall be defined as an area that does
not place ground ladders over openings such as windows or doors, and are located at
strong points of building construction in locations where the access point does not
conflict with overhead obstructions such as tree limbs, wires, or signs.
605.11.3.2 Residential systems for one-and two-family residential dwellings. Access
shall be provided in accordance with Sections 605.11.3.2.1 through 605.11.3.2.4
605.11.3.2.1 Access required Residential. Panels /modules shall be located in a
manner that provides a minimum of two separate 3 foot (914 mm) wide clear
access pathways from the eave to the ridge on each roof. The access pathways
shall be located at structurally strong locations on the building capable of
supporting the live load of fire fighters accessing the roof.
605.11.3.2.2 Residential buildings with a single ridge. Panels/modules shall be
pennitted to be located up to the ridge on one roof slope only, with the other slope
accessible and suitable for ventilation up to the ridge or alternative method
approved by AHJ.
605.11.3.2.3 Residential buildings with multiple ridges, hips or valleys:
Panels/modules shall be located no closer than 18 inches (457 mm) to a ridge, hip
or a valley if panels/modules are to be placed on both sides of a ridge, hip or
valley. If the panels are to be located on only one side of a ridge, hip or valley
then the panels shall be pennitted to be placed directly adjacent to the ridge, hip
or valley.
605.11.3.2.4 Smoke Ventilation. Panels/modules shall be located such that one
side of each ridge shall have not less than 4 feet (1290mm) of clear space
immediately below the ridge available to allow for fire department smoke
ventilation operations.
605.11.3.3 All other occupancies. Access shall be provided in accordance with Sections
605.11.3.3.1 through 605.11.3.3.3.
Exception: Where it is determined by the fire code official that the roof configuration is
similar to a one-or two-family dwelling, the fire code official may approve the
ORDINANCE Page 9 of 13
glmv/M V·11·021/IFClOrd Ch 9 04 Fire Code 07·22·' J F
residential access and ventilation requirements provided In 605.11.3.2.1 through
605.11.3.2.4.
605.11.3.3.1 Access. There shall be a mInImum 6 foot (1829 mm) wide clear
perimeter around the edges of the roof.
Exception: If either axis of the building is 250 feet (76 200 mm) or less, there
shall be a minimum 4 foot (1290 mm) wide clear perimeter around the edges of
the roof or alternative method approved by AHJ.
605.11.3.3.2 Pathways. The solar installation shall be designed to provide designated
pathways. The pathways shall meet the following requirements:
1. The pathway shall be over areas capable of supporting the live load of fire
fighters accessing the roof
2. The center line axis pathways shall be provided in both axis of the roof.
Center line axis pathways shall run where the roof structure is capable of
supporting the live load of firefighters accessing the roof.
3. Shall be straight line not less than 4 feet (1290 mm) clear to skylights and/or
ventilation hatches
4. Shall be straight line not less than 4 feet (1290 mm) clear to roof
standpipes
5. Shall provide not less than 4 feet (1290 mm) clear around roof access hatch
with at least one not less than 4 feet (1290 mm) clear pathway to parapet or
roof edge
605.11.3.3.3 Smoke Ventilation. The solar installation shall be designed to meet the
following requirements:
I. Arrays shall be no greater than 150 feet (45 720 mm) by 150 feet (45 720 mm)
in distance in either axis in order to create opportunities for smoke ventilation
operations.
2. Smoke ventilation options between array sections shall be one of the following:
2.1. A pathway 8 feet (2438 mm) or greater in width;
2.2. A 4 feet (1290 mm) or greater in width pathway and bordering roof
skylights or smoke and heat vents~
2.3. A 4 feet (1290 mm) or greater in width pathway and bordering 4 foot
(1290 mm) x 8 foot (2438 mm) "venting cutouts" every 20 feet (6096
mm) on alternating sides of the pathway
605.11.4 Ground mounted photovoltaic arrays. Ground mounted photovoltaic arrays shall
comply with Sections 605.11 through 605.11.2 and this section. Setback requirements do not
apply to ground-mounted, free standing photovoltaic arrays, except as provided in Chapter
22C MMC. A clear brush area of 10 feet (3048 mm) is required for ground mounted
photovoltaic arrays.
ORDINANCE Page 10 of 13
g/mv/MV-11-021 /IFC/Ord Ch 904 Fire Code 07-22-1 IF
9.04.0902 International Fire Code Section 902. 1 Definitions is amended.
The definition of fire area is amended by adding: "For Section 903, the definition of FIRE
AREA shall be as follows: The aggregate floor area enclosed and bounded by exterior walls of a
building."
(Formerly 9.04.086; Ord. 2739 § 1,2008; Ord. 2532 § 7,2004; Ord. 2377 § 9,2001).
9.04.0903 International Fire Code Section 903.2 amended -Sprinkler systems -Where
required.
Amend Section 903.2 by adding items:
Existing buildings altered such that the total fire area square footage exceeds the
threshold square footage for each occupancy group listed in this section shall be provided
with an automatic sprinkler system. Where there is a change-of-occupancy classification
in an existing building, the sprinkler requirements for the new occupancy classification
shall apply.
An automatic sprinkler system shall be provided throughout buildings where the
combined area of all fire areas on all floors, including any mezzanines, exceeds the
threshold square footage for each occupancy group listed in this section.
(Formerly 9.04.090; Ord. 2739 § 1,2008; Ord. 2532 § 8,2003).
9.04.0903.2.1 International Fire Code Section 903.2.1 amended -Sprinkler systems
Group A occupancies.
Section 903.2.1.1 Item I. Replace 12,000 with 8,000.
Section 903.2.1.3 Item 1. Replace 12,000 with 8,000.
Section 903.2.1.4 Item 1. Replace 12,000 with 8,000.
(Formerly 9.04.079; Ord. 2739 § 1,2008; Ord. 2532 § 7,2004; Ord. 2377 § 2, 2001).
9.04.0903.2.3 International Fire Code Section 903.2.3 amended -Sprinkler systems
Group E occupancies.
An automatic sprinkler system shall be provided for Group E Occupancies.
Delete items 1 and 2, and the Exception, and replace them with the following:
Exceptions:
I. Portable school classrooms, provided aggregate area of any cluster or portion of a
cluster of portable school classrooms does not exceed 5,000 square feet; and clusters of
portable school classrooms shall be separated as required by the building code.
2. Group E Occupancies with an occupant load of 50 or less, calculated in accordance
with table 1004.1.1.
(Formerly 9.04.080; Ord. 2739 § 1,2008; Ord. 2532 § 7, 2004; Ord. 2377 § 3,2001).
9.04.0903.2.4 International Fire Code Section 903.2.4 amended -Sprinkler systems
Group F-l occupancies.
ORDINANCE Page 11 of 13
glmv/MV-II-021IlFC/Ord Ch 904 Fire Code 07-22-11 F
Section 903.2. Item 1. Replace 12,000 with 8,000.
Section 903.2. Item 3. Replace 24,000 with 8,000.
Section 903.2.4. Item 4. Where a Group F-2 fire area exceeds 8,000 square feet.
(Formerly 9.04.081; Ord. 2739 § 1,2008; Ord. 2532 § 7,2004; Ord. 2377 § 4, 2001).
9.04.0903.2.7 International Fire Code Section 903.2.7 amended -Sprinkler systems
Group M and B occupancies.
Section 903.2.7 Item 1. Add B after M and change 12,000 to 8,000.
Section 903.2.7 Item 2. Add B after M.
Section 903.2.7 Item 3. Add B after M and change 24,000 to 8,000.
(Formerly 9.04.083; Ord. 2739 § 1,2008; Ord. 2532 § 7, 2004; Ord. 2377 § 6, 2001).
9.04.0903.2.8 International Fire Code Section 903.2. 8 amended -Sprinkler systems
Group R occupancies.
Amend Section 903.2.8 to add:
An automatic sprinkler system shall be installed throughout every apartment house three (3) or
more stories in height or containing five (5) or more dwelling units, townhomes and every
congregate residence three (3) or more stories in height or having an occupant load of five (5) or
more, and every hotel three or more stories in height or containing five (5) or more guest rooms,
and one and two family dwelling units three (3) or more stories. Residential or quick-response
standard sprinklers shall be used in the dwelling units and guest room portions of the building
shall be protected with an automatic sprinkler system per 903.3.1.3.
(Formerly 9.04.084; Ord. 2739 § 1,2008; Ord. 2532 § 7, 2004; Ord. 2377 § 7,2001).
9.04.0903.2.9 International Fire Code Section 903.2.9 and 903.2.10 amended -Sprinkler
systems -Group S occupancies.
Section 903.2.9 is hereby enacted and added to the International Fire Code as previously enacted
and amended by the city reading as follows:
Section 903.2.9 Group S Occupancies. An automatic sprinkler system shall be installed
throughout all Group S occupancies that have 8,000 square feet or more of fire area.
Section 903.2.9. add item 5: "In all Group S-1 mini-storage occupancies."
Section 903.2.9.1. add item 5: "Repair garages where the use of open flame or welding is
conducted with a fire area exceeding 3,000 square feet."
Replace all occurrences of "S-1 " with "S".
Section 903.2.9 Item 1. Replace 12,000 with 8,000.
Section 903.2.9 Item 3. Replace 24,000 with 8,000.
Section 903.2.9 add item 5: "In all Group S-1 mini-storage occupancies."
ORDINANCE Page 12 of 13
glmv/MV-11-021/1 FC/Ord Ch 9 04 Fire Code 07-22-11 F
Section 903.2.9.1 Item 1. Replace 10,000 with 8,000.
Section 903.2.9.1 Item 2. Replace 12,000 with 8,000.
Section 903.2.9.1 add item 5: "Repair garages where the use of open flame or welding is
conducted with a fire area exceeding 3,000 square feet."
Section 903.2.9.2 Replace 20,000 with 8,000.
Section 3. Severability. If any section, subsection, sentence, clause, phrase or word of this
ordinance should be held to be invalid or unconstitutional by a court of competent jurisdiction,
such invalidity or unconstitutionality thereof shall not affect the validity or constitutionality of
any other section, subsection, sentence, clause, phrase or word of this ordinance.
Section 4. Effective Date. This ordinance shall become effective five days after the date of its
publication by summary.
~
PASSED by the City Council and APPROVED by the mayor this ~ L( day of Vet. ,
2011.
CITY OF MARYSVILLE
'GJ{
Jon Nehring, Mayor
O'Brien, Deputy City Clerk
APPROVED AS TO FORM ,&d=~.L61 QJ-:.O
Grant K. Weed, City Attorney.
Date of Publication: ~J.4I1------,\--,-\lBJ 1\
ORDINANCE Page 13 of 13