Loading...
HomeMy WebLinkAboutR-1405 - Adopting Marysville Fire Department Standards relating to sprinkler and alarm system installation•., CIT Y 0 F MAR Y S V ILL E Marysville,Washington RESOLUTION NO.IlfoS- A RESOLUTION OF THE CITY OF MARYSVILLE ADOPTING MARYSVILLE FIRE DEPARTMENT STANDARDS RELATING TO SPRINKLER AND ALARM SYSTEM INSTALLATION. BE IT RESOLVED BY THE CITY COUNCIL OF THE CITY OF MARYSVILLE,WASHINGTON AS FOLLOWS: The City Council hereby approves and adopts the attached copy of Marysville Fire Department Standard #3 entitled: Guidelines for sprinkler and alarm system installation for Residential Division 1 Occupancies where required by UBC Section 3802(H)and/or UFC section 14.104(C), 1988 Editions. PASSED BY THE CITY COUNCIL AND APPROVED BY THE MAYOR THIS RQl~DAY OF ::sp-",Y0:!:J ,19~. ayor Attest: c;;w¥~Cit~Clerk Approved as to form: N. V ?~~,a<C$~--vr ~City Atoey Resolution MARYSVILLE FIRE DEPARTMENT STANDARD #3 Standard for sprinkler and alarm system installation for Residential Division 1 Occupancies where required by 3802 (H),UBC and 14.104 (C) UFC,1988 Editions. GENERAL REQUIREMENTS:Sprinkler systems located wi thin the City of Marysville shall meet the criteria as set forth in the 1988 Uniform Fire Code,the 1988 Uniform Building code,and the following: 1).All systems shall be designed,drawn,and installed by a licensed sprinkler contractor.The designer shall be at least a NICET Level II Residential Design Specialist.When requested,.a copy of the technicians certification from NICET shall be submitted to the Marysville Fire Department. 2).The sprinkler system design shall be reviewed by an approved outside agency prior to approval by the Marysville Fire Department. 3).The sprinkler system shall,as a mInImum meet the requirements set forth in NFPA 13R ·Standard for the Installation of Sprinkler Systems in Residential Occupancies up to Four Stories in Height.· 4).Fixed temperature heat detectors shall be installed in areas not required to be protected by the sprinkler system.These areas may include bathrooms,attics,penthouse equipment rooms, and elevator shafts.Small clothes closets as defined in NFPA 13R,Chapter 2-6,Exception No.2,will be exempt. SPECIAL REOUIREMENTS 1).The sprinkler system and fire alarm system shall be supervised by an approved local U.L.Listed alarm agency when the total number of sprinkler heads and heat detectors meet or exceed 100.Provide a valid contract with an alarm agency prior to occupancy. 2).Provide a copy of a valid contract for maintenance,emergency repair,and annual testing and certification of the sprinkler and alarm system.This contract shall be required to take effect at the completion of the warranty period. 3).A fire alarm control panel is required for receiving flow alarms,trouble signals,any other signals generated from components of sprinkler systems,and fire alarm system signals,shall be located on the project site and shall be U.L.Listed for that use.The fire alarm panel shall show zones as approved by the Fire Marshal. Page 1 of 3 •,.'" 4).At least one 2 1/2"inch fire department connection shall be provided when the sprinkler system has 20 sprinklers or more.The fire department connection shall be located adjacent to fire department apparatus access.The location shall be approved by the Fire Marshal.The distance between the fire department connection and a hydrant shall be 30 feet or less. Fire Department connections located in areas subject to vehicular damage shall be protected by means of guard posts per Fire Marshals approval. All Fire Department connections shall be painted red on the portion of the standpipe which protrudes above the ground. The clappered brass portion may remain unpainted.All connections shall be labeled in accordance with NFPA standards. 5).All sprinklered bUildings shall provide a dedicated space with a locked access door on an exterior wall to contain the sprinkler equipment.This space may contain other equipment,such that it does not interfere with access to or the operation of sprinkler equipment.An approved key box shall be provided with a key that will gain access to the sprinkler equipment space only. 6).An approved metered double detector check valve shall be required in all sprinkler systems.(See Public Works Department for specifications and information). 7).All automatic initiating devices shall be located and installed per the manufacturer's specifications and NFPA 72E current edition and shall have a performance test per NFPA 72H current edition. 8).Audible signaling devices shall be provided,as per NFPA 72A, such that upon an alarm being received by the fire alarm panel, all occupants of the building shall be alerted. 9).The fire alarm panel shall have a dedicated circuit as its source of power.This circuit shall not be connected to a tenants electrical panel. 10).All fire alarm panels shall be installed in such a manner that they are protected from weather or moisture. Page 2 of 3 I J •.>... 11).Annunciator panels shall be provided and located so as to be readily accessible to Fire Department personnel. 12).Smoke detectors in sleeping areas as required by Uniform Building Code Section 1210(a)shall not be connected to the fire alarm system. Page 3 of 3